Optimalisasi Kinerja Proteksi Recloser Jaringan Distribusi 20kV Penyulang RDT03 Menggunakan Algoritma Particle Swarm Optimization
Abstract
The reliability of an electric power distribution network system is very important to ensure a good quality of service for consumers. The focus of this study is to find the optimal protection coordination design, topology and operating scheme for RDT03 refiners in the Tambak Aji Industrial Estate. To show the level of reliability and continuity of the electric power distribution network, the SAIFI index (System Average Interruption Frequency Index) and the SAIDI index (System Average Interruption Duration Index) are used. The existing recloser located in section 25 resulted in a SAIFI value of 0.8933 and a SAIDI of 2.407. Using the PSO (Particle Swarm Optimization) optimization method, the results were obtained that the Best Fitness for the most optimal recloser placement was in section 29 with a SAIFI value of 0.32575 and a SAIDI value of 1.0558. This change in recloser placement resulted in a decrease in SAIFI by 36% or by 0.5675 times / year / customer and a decrease in the value of SAIDI by 43.61% or by 1.3649 hours / year / customer. Thus, there is an increase in network reliability if the recloser at the RDT03 feeder is relocated to the location of section 29.
Keywords: Reliability, Recloser, SAIFI, SAIDI, Particle Swarm Optimization
ABSTRAK
Keandalan suatu sistem jaringan distribusi tenaga listrik merupakan hal yang sangat penting untuk menjamin mutu pelayanan yang baik bagi konsumen. Fokus dari penelitian ini adalah untuk mencari desain koordinasi proteksi, topologi dan skema operasi yang optimal untuk penyulang RDT03 di Kawasan Industri Tambak Aji. Untuk menunjukkan tingkat keandalan dan kontinuitas jaringan distribusi tenaga listrik digunakan indeks SAIFI (System Average Interruption Frequency Index) dan indeks SAIDI (System Average Interruption Duration Index). Hasil optimalisasi menggunakan PSO (Particle Swarm Optimization), didapatkan hasil bahwa Best Fitness untuk penempatan recloser yang paling optimal adalah pada section 29 dengan nilai SAIFI sebesar 0.32575 dan nilai SAIDI sebesar 1.0558. Dengan menggunakan PSO, diperoleh lokasi letak recloser yang baru dengan nilai SAIFI yang lebih optimal dengan penurunan sebesar 36% atau sebesar 0,5675 kali/tahun/pelanggan dan penurunan nilai SAIDI sebesar 43,61% atau sebesar 1,3649 jam/tahun/pelanggan. Jika dibandingkan dengan letak recloser exsisting, recloser existing terletak pada section 25 dengan nilai SAIFI sebesar 0,8933 dan SAIDI sebesar 2,407. Dengan demikian terdapat peningkatan keandalan jaringan jika recloser pada penyulang RDT03 direlokasi menuju lokasi section 29.
Keywords
Full Text:
PDFReferences
Amirudin, M. Hasyim, Optimalisasi Keandalan Sis-tem Proteksi Feeder dengan Relay Penutup Balik (Auto Recloser) Pada Gardu Induk Tello, Gowa: Jurnal Instek Vol. 5, No. 1, 2020.
Dinna Fitria, Arif Maulana, Analisis Pembagian Zona Proteksi Pada Jaringan Distribusi 20 kV Penyulang Meranti GI Bungaran Untuk Meningkatkan Pela-yanan Ke Konsumen, Palembang: Jurnal Ampere, Volume 5, No 2, 2020
D. Trebolle and B. Valecillos, “Optimal Operation of Paraleled Power Transformers,” Renew. Energy Pow-er Qual. J., vol. 1, Mar. 2008, doi: 10.24084/repqj06.392.
Fahrulrozi, Moch.; Suyono, Hadi & Lomi, Abraham (2019). Peningkatan Keandalan Sistem Distribusi dengan Relokasi Penempatan Fuse-Recloser Optimal karena Injeksi Pembangkit Tersebar, Jurnal EECCIS Vol. 13, No. 2, Agustus, pp.78-83, p-ISSN : 1978-3345, e-ISSN(Online): 2460-8122, https://jurnaleeccis.ub.ac.id/
Hidayah, Nurul; Supriyatna dan Muljono, Agung Budi (2014). Analisis Manuver Jaringan Terhadap Keandalan Kontinuitas Penyaluran Tenaga Listrik Penyulang Di Area Ampenan [Analysis of Network Maneuvers Toward Continuity Reliability of Feeders Electric Power Transmission in Ampenan Area], Diel-ektrika, ISSN 2086-9487 109 Vol.3, No.1, pp.109 -115, Agustus.
Khairul, Fadjri & Risfendra (2022), Evaluasi Keanda-lan Sistem Jaringan Distribusi 20 kV dan Energy Not Supplied (ENS) Pada GH Balai Selasa, JTEIN: Jurnal Teknik Elektro Indonesia Vol.3, No.1, 2022, pp.158-167, e-ISSN 2723-0589, DOI: https://doi.org/10.24036/jtein.v3i1.226
Marsudi, D. (2006). Operasi Sistem Tenaga Listrik. Yogyakarta: Graha Ilmu
Putra, I Gede Wiyoga; Arjana, I Gede Dyana dan Setiawan, Widyadi (2020). Perancangan Penem-patan Recloser Yang Optimum Menggunakan Metode Quantum Genetic Algorithm Di Penyulang Palapa, Jurnal Spektrum, Vol. 7, No. 4 Desember, pp.90-99.
Senen, Adri ; Ratnasari, Titi & Anggaini, Dwi (2019), Studi Perhitungan Indeks Keandalan Sistem Tenaga Listrik Menggunakan Graphical User Interface Matlab pada PT PLN (Persero) Rayon Kota Pinang, Jurnal Ilmiah: Energi dan Kelistrikan, Vol. 11, No. 2, Juli – Desember, pp.138-148, P-ISSN 1979-0783, E-ISSN 2655-5042, http://doi.org/10.33322/energi.v11i2.497.
Slamet Hani, Gatot Santoso, Penempatan Recloser Sebagai Parameter Keandalan Sistem Proteksi pada Sistem Distribusi, Yogyakarta: Simposium Nasional RAPI XVIIII FT UMS, 2019.
Wayan Sukadana, Nyoman Suartika, Optimalisasi LBS Motorized Key Point Pada Jaringan Distribusi 20 KV untuk Meningkatkan Keandalan Sistem, Bali: Jurnal Tenik Elektro dan Vokasional, Vol. 5, No. 1.1, 2019
Zahro, Hani Zulfia & Wahyuni, Febriani Santi (2020). Optimasi Particle Swarm Optimization (PSO) untuk Penetuan Base Tranciever System (BTS), Jurnal Mnemonic, Vol 3, No.1, Februari.
DOI: http://dx.doi.org/10.26623/elektrika.v15i1.5623
Refbacks
- There are currently no refbacks.
This work is licensed under a Creative Commons Attribution 4.0 International License.