ANALISA PENGUJIAN PARTIAL DISCHARGE PADA KUBIKEL TD #1 MENGGUNAKAN METODE TRANSIENT EARTH VOLTAGE DI GARDU INDUK MUARA BUNGO
DOI:
https://doi.org/10.26623/elektrika.v17i1.10382Keywords:
Gardu Induk Muara Bungo, Partial Discharge, Pemutus Tenaga (PMT), Sensor TEV, Ultra TEV Plus 2Abstract
Muara Bungo Main Substation is one of the main substations in the working area of PT. PLN (Persero) UPT Jambi. This substation is located along the Sungai Binjai, Batin III District, Bungo Regency, Jambi Province. The Power Transformer 1 cubicle panel at this substation often experiences problems with insulation defects which can cause interference with electricity transmission. In this research, the transient earth voltage method is applied, which functions as a sensor to detect partial discharge signals in high voltage equipment. The sensor used to measure transient ground voltage is a capacitive sensor. This testing can be done directly (online) without disrupting operations. The measuring instrument used in partial discharge testing is the Ultra TEV Plus 2.The results of partial discharge testing using the transient earth voltage method show that most of the panels and their components, especially panel TD No. 1, in good condition. However, there is one component, namely the circuit breaker (PMT), which shows the highest partial discharge value. Tests on Palem feeder cubicles showed the highest TEV value of 12 dB and PPC of 4.62 for the PMT component. Overall, the measured TEV values ranged from 10 to 19 dB, and the PPC ranged from 0.5 to 6, indicating that the Palem feeder cubicles were classified as low-level PD. Based on these results, every PMT component in the field needs to be checked thoroughly and repairs planned if there are problems with the PMT material.
Keywords: Circuit Breaker (PMT), Muara Bungo Substation, Partial Discharge, TEV Sensor, Ultra TEV Plus 2
ABSTRAK
Gardu Induk Muara Bungo adalah salah satu gardu induk dari wilayah kerja PT. PLN (Persero) UPT Jambi. Gardu ini berada di sepanjang Sungai Binjai, Kecamatan Batin III, Kabupaten Bungo, Provinsi Jambi. Panel kubikel Trafo Daya 1 di gardu ini sering mengalami masalah cacat isolasi yang bisa menyebabkan gangguan pada transmisi listrik. Dalam penelitian ini diterapkan metode transient earth voltage, yang berfungsi sebagai sensor untuk mendeteksi sinyal pelepasan sebagian pada peralatan tegangan tinggi. Sensor yang digunakan untuk mengukur tegangan tanah transien adalah sensor kapasitif. Pengujian ini dapat dilakukan secara langsung (online) tanpa mengganggu operasional. Alat ukur yang dipakai dalam pengujian pelepasan sebagian adalah Ultra TEV Plus 2. Hasil pengujian pelepasan sebagian dengan metode transient earth voltage menunjukkan bahwa sebagian besar panel dan komponennya, khususnya panel TD No. 1, dalam kondisi baik. Namun, terdapat satu komponen, yaitu pemutus arus (PMT), yang menunjukkan nilai pelepasan sebagian paling tinggi. Pengujian pada kubikel penyulang Palem menunjukkan nilai TEV tertinggi sebesar 12 dB dan PPC sebesar 4,62 untuk komponen PMT. Secara keseluruhan, nilai TEV yang terukur berkisar antara 10 hingga 19 dB, dan PPC antara 0,5 hingga 6, menandakan bahwa kubikel penyulang Palem tergolong dalam kategori PD tingkat rendah. Berdasarkan hasil ini, setiap komponen PMT di lapangan perlu diperiksa secara menyeluruh dan direncanakan perbaikannya jika terdapat masalah pada material PMT.
References
[I] Novemsa, “Analisis Keandalan Konduktor Ku-bikel Penyulang Outgoing Menggunakan Alat Ukur Partial Discharge Pada PT. PLN (Persero) Gardu In-duk Rengat,” 2022.
[2] C. D. Yusri, “Karakteristik Partial Discharge Pada Permukaan PCB (Epoxy Resin) Menggunakan El-ektroda Plat-Batang,” 2023.
[3] V. Savira, “Analisa Data Kontrol Suhu dan Kelem-bapan pada Kubikel Gardu Distribusi Pasang Dalam Berbasis Mikrokontroller”.
[4] T. Sugiono and Firdaus, “Analisa Pola dan Spektrum Partial Discharge Terhadap Kerusakan Transforma-tor,” vol. 7, p. 2, Jul. 2020.
[5] A. T. Mustari, S. Pranoto, and T. Tadjuddin, “Ana-lisis Rugi-rugi Daya Akibat Kerusakan Jointing Me-lalui Hotspot Thermovision Pada PT. PLN (Persero) Unit Layanan Pelanggan Rantepao,” in Seminar Na-sional Teknik Elektro dan Informatika (SNTEI), 2021, pp. 93–97.
[6] R. T. Jurnal, “Studi Analisis Pengaruh Partial Dis-charge Pada Sktm Terhadap Kehandalan Penyu-lang: Supriadi Legino, Firman Jurjani,” Energi & Kelistrikan, vol. 8, no. 2, pp. 67–73, 2016.
[7] J. Anggriawan, “Analisa Pengujian Jointing Cable Dengan Tegangan Pengenal 12/20 (24) Kv Menggunakan Tegangan Impuls Dan Partial Dis-charge (suatu studi laboratorium di PT.PLN Puslit-bang ),” Universitas Negeri Jakarta, May 2022.
[8] R. S. Sipahutar, “Pendeteksian dan Identifikasi Jenis Partial Discharge Dengan Metode Analisa Pola Phase Resolved Partial Discharge (PRPD),” 2021.
[9] M. Mika, L. S. Patras, and F. Lisi, “Perancangan Pendeteksi Partial Discharge Pada Isolasi Padat,” Jurnal Teknik Elektro dan Komputer, vol. 8, no. 3, pp. 161–170, 2019.
[10] “Ultra TEV Plus 2,” PT. Multi Inovasi Teknologi. Ac-cessed: Jan. 15, 2024. [Online]. Available: https://multiinovasiteknologi.com/ultra-tev-plus-2/#:~:text=Ultra%20TEV%20Plus%202%20merupakan,dll)%20yang%20terletak%20pada%20kubile.
[11] G. A. P. Yoga, “Analisa Keandalan Sistem Tenaga Listrik Di Wilayah Lampung Berdasarkan Ketersedi-aan Daya Pada Tahun 2016,” 2017.
[12] J. N. V. Wasida, L. S. Patras, and G. M. C. Man-gindaan, “Analisa Efek Korona pada Saluran Transmisi Gardu Induk Paniki,” 2022.
Downloads
Published
Issue
Section
License
Copyright (c) 2025 Elektrika

This work is licensed under a Creative Commons Attribution-NonCommercial-ShareAlike 4.0 International License.
Authors who publish this journal agree to the following terms:
The author owns the copyright and grants the journal the first publication rights with the work simultaneously licensed under the Creative Commons Attribution 4.0 International License which allows others to share the work with recognition of the authorship of the work and initial publication in the journal.
Authors may enter into separate additional contractual agreements for non-exclusive distribution of the published journal version of the work (e.g., posting it to an institutional repository or publishing it in a book), in recognition of its initial publication in this journal.
Authors are allowed and encouraged to post their work online (e.g., in institutional repositories or on their websites) before and during the submission process, as it can lead to productive exchanges, as well as earlier and larger citations of published works (See The Effects of Open Access).

This work is licensed under the Creative Commons Attribution 4.0 International License.